1. The main functions of the lightning arrester intelligent monitoring meter are:
Automatic monitoring function
Periodic automatic monitoring of the full current, number of actions, and action time of the lightning arrester.
Data storage function
It has the function of saving and exporting historical data, and can automatically store 10000 monitoring data periodically.
communication function
Equipped with RS485 data upload function, meeting the MODBUS protocol.
alarm function
Equipped with abnormal alarm function, real-time alarm will be triggered when monitoring data exceeds the standard, monitoring function fails, communication interruption and other abnormalities occur. The alarm settings can be modified, and the alarm information can be transmitted remotely in real time.
Local display function
The lightning arrester action count is displayed using a 3-digit electromagnetic counter. The full current is displayed on a scale. The scale has a normal area (green), a caution area (yellow), and an alarm area (red).
Scale indication |
serial number |
Full current range |
status display |
status judgment |
one |
0.5-2.5mA |
green |
normal |
two |
2.5-3.5mA |
yellow |
Attention |
three |
3.5-5mA |
red |
call the police |
Table 1
Meter appearance
The device adopts a meter style appearance structure, which is consistent with the installation size of traditional lightning arrester monitors and can be directly replaced for installation.
?
1. Technical indicators for digital leakage current meter of lightning arrester:
Product Features |
Description |
Ambient Temperature |
-40℃~+70℃ |
relative humidity |
5%~95% |
atmospheric pressure |
80 kPa to 110 kPa |
Applicable voltage level |
Voltage level of 35kV and above |
Residual pressure test |
Less than 3% of the residual voltage of the equipped lightning arrester, with a maximum not exceeding 3.0kV |
High current impulse withstand test |
100kA |
Square wave impulse current withstand test |
600A (optional) |
Full current measurement range |
100uA~5mA |
Maximum allowable measurement error for full current |
± (standard reading * 1%+5uA) |
Full current measurement repeatability |
RSD<0.5% |
Number of lightning arrester actions |
0~999 |
Data update frequency |
5 S/time |
Number of data storage entries |
10000 pieces |
Full current display on the scale |
Normal zone (green), Attention zone (yellow), and Alarm zone (red) |
power supply method |
Pa:AC 220(1±10%)V,頻率 50(1±5%)Hz
Pb:DC 220(1±10%)V、±12V、0~24V
|
Device power consumption |
<5VA |
Protection level |
IP66 |
service life |
16 years |
Installation method |
Screw fixation |
weight |
3.6kg |
2. Electromagnetic compatibility performance
Testing Standard |
level |
criteria for judgment |
GB/T 17626.2 Electrostatic Discharge (ESD) |
Level 4 |
?A/B |
GB/T 17626.3 Radio frequency electromagnetic field radiation |
Level 3 |
?A |
GB/T 17626.8 Power Frequency Magnetic Field |
Level 5 |
?A |
GB/T 17626.9 Pulse Magnetic Field |
Level 5 |
?A |
GB/T 17626.10 Damping oscillating magnetic field |
Level 5 |
?A |
GB/T 17626.11 Voltage sag |
Category 3 |
?A/B |
GB/T 17626.4 Electrical Fast Transient Pulse Group |
Level 4 |
?A/B |
GB/T 17626.5 Surge (Impact) |
Level 4 |
?A/B |
GB/T 17626.6 Conducted disturbances induced by radio frequency fields |
Level 3 |
?A |